Local Energy CodeAll air-conditioned buildings in Singapore must comply with the local energy standards. During the building plan submission stage, the OTTV and U-value calculations are submitted to the Building Construction Authority for approval. The Certificate of Statutory Completion for the building is issued after the works have been completed in accordance with the approved plans. Some of the standards are presented below: For details on the local energy standards, please refer to:
HVACIndoor Design Conditions for A/C space
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Roof U-value max (W/m2°K) |
|||
|
Type |
Weight Range (kg/m2) |
A/C |
Non A/C |
|
Light |
Under 50 |
0.5 |
0.8 |
|
Medium |
50 to 230 |
0.8 |
1.1 |
|
Heavy |
Over 230 |
1.2 |
1.5 |
Table 1
Building Interior Lighting
|
Type of usage |
Maximum lighting power budget (Watts/m2) |
|
Offices |
15 |
|
Classrooms |
15 |
|
Lecture theatres |
15 |
|
Auditoriums / Concert halls |
10 |
|
Shops / Supermarkets / Departmental stores (including general, accent & display lighting) |
25 |
|
Restaurants |
15 |
|
Lobbies / Atriums / Concourse |
10 |
|
Stairs / Corridors |
10 |
|
Car Parks |
5 |
|
Electronic manufacturing and fine detail/Assembly industries |
20 |
|
Medium and heavy industries |
15 |
|
Warehouses / Storage areas |
10 |